Technical Specification
MODEL EPI20K
Capacity (VA/Watts) 15kVA/12kW
INPUT
Operating voltage range 380Vac(±20%), (3Ph+N+PE)
Operating frequency range 50/60Hz(±5%)
Power Factor >0.97 (with filter)
Max. input current (A) 45
OUTPUT
Output Voltage 220Vac(±0.5%)
Output frequency 50/60Hz(±0.5%)
Crest factor 3:1 (max)
Efficiency 6~8KVA: 85% online 10~40KVA: 90% online
Harmonic Distortion (THDv) ≤1.5% with linear load
BATTERY
Battery voltage 192Vdc 240Vdc
SYSTEM FEATURES
Transfer time 0ms (Line mode →Battery mode)
Overload ≤125% /10min, ≤150%/200ms
LED display Low battery voltage, Mains status, Inverter, Bypass, UPS failure, Overload
LCD display I/O voltage, Frequency, Battery voltage, Load percentage,Internal temperature
Communication interface RS232, SNMP (optional), Dry contact(optional)
ENVIRONMENT
Operating Temperature 0℃~40℃
Storage temperature -25~55℃
Humidity range 0~95% (non-condensing)
Altitude <1500m
Noise level <55dB
PHYSICAL
Dimension W×D×H (mm) 305×585×864 430×830×1100
Net Weight (S/H) (kg) 155
STANDARDS
Safety IEC/EN62040-1;IEC/EN60950-1
EMC
IEC/EN62040-2;IEC61000-4-2;IEC61000-4-3;IEC61000-4-4; EC61000-4-5;IEC61000-4-6;IEC61000-4-8
Reviews